Specifications
Ethernet Communication
- Protocols EtherNet/IP, OPC UA, PROFINET, Modbus TCP
§ Number of Ports 4
- Speed 10/100 Mbps, Auto MDI/MDIX
- Connector 8-pin RJ45
- Protection Built-in 5 kV magnetic isolation
Serial Communications
- Port Type RS-232/422/485, software-selectable
§ No. of Ports 2
- Protocol Modbus RTU
- Port Connector DB9 male
- Data Bits 5, 6, 7, 8
- Stop Bits 1, 1.5, 2
- Parity None, odd, even, space, mark
- Flow Control XON/XOFF, RTS/CTS
- Baud Rate 50 bps ~ 921.6 kbps
- Serial Signals RS-232: TxD, RxD, CTS, RTS, DCD, RI, GND
RS-422: TxD+, TxD-, RxD+, RxD-, GND RS-485: Data+, Data-, GND
Software
§ Modbus RTU/TCP
Mode Client
Functions Support 1, 2, 3, 4, 5, 6, 15, 16, 23 Max. Number of Connections EtherNet/IP: 64
PROFINET: 64
OPC UA: 1400
§ EtherNet/IP
Class Adapter
Max. Number of Connections 32 explicit messaging, 5 implicit messaging Max. Total I/O Data Size Input: 496 bytes
Output: 496 bytes
PROFINET
- Type IO-Device
- Slot 64
- Cyclic data exchange 8 ms cycle time
- Total I/O Data Size Input: 512 bytes
Output: 512 bytes
OPC UA
- Type Server
- Number of Connections 128 connections
- Total I/O Data Size Input: 8192 bytes
Output: 8192 bytes
General
- LED Indicators System: power, system status, protocol status LAN: speed, link/active, error
- Reboot Trigger Built-in WDT
- MicroSD Card Configuration backup and restore
Mechanics
- Dimensions (W x H x D) 42 x 140 x 95 mm (1.66" x 52" x 3.75")
- Enclosure Metal with solid mounting hardware
- Mounting DIN rail, wall
- Weight 497 Kg
Power Requirements
- Power Input 12 ~ 48 VDC, redundant dual inputs
- Power Connector Terminal block
- Power Consumption 2 W
Environment
- Operating Temperature -40 ~ 75 °C (-40 ~ 167 °F)
- Storage Temperature -40 ~ 85 °C (-40 ~ 185 °F)
- Operating Humidity 10 ~ 95% RH
Regulatory Approvals
- EMC CE, FCC Part 15 Subpart B (Class A)
Ordering Information
- EKI-1242IEIMS-A Industrial Fieldbus Gateway