Specifications
Analog Input
Channels 8 (differential)
Input Impedance > 10 MΩ
lnput Type Thermocouple
Thermocouple Type and Range:
J 0 ~ 760°C R 500 ~ 1,750°C
K 0 ~ 1,370°C S 500 ~ 1,750°C
T -100 ~ 400°C B 500 ~ 1,800°C
E 0 ~ 1,000°C
Accuracy ±0.1%
Span Drift ±25 ppm/°C
Zero Drift ±6 μV/°C
Resolution 16-bit
Sampling Rate 10 sample/ second (total)
CMR @ 50/60 HZ 90dB
NMR @ 50/60 HZ 60dB
Wire Burnout Detection
Digital Output
Channels 8, open collector to 30 V,
100 mA max. load
Power Dissipation 300 mW for each module
Ordering Information
ADAM-6018 8-ch Isolated
Thermocouple Input
Modbus TCP Module w/
8-ch DO
Common Specifications
General
LAN 10/100Base-T(X)
Power Consumption 2.5 W @ 24 VDC (ADAM-6015)
2.7 W @ 24 VDC (ADAM-6017)
2 W @ 24 VDC (ADAM-6018)
Connectors 1 x RJ-45 (LAN), Plug-in screw
terminal block (I/O and power)
Watchdog System (1.6 second) and
Communication (programmable)
Power Input 10 ~ 30 VDC
Supports Peer-to-Peer
Supports GCL
Supports Modbus/TCP, TCP/IP, UDP, HTTP and
MQTT (ADAM-6017) Protocols
Protection
Over Voltage ±35 VDC
Protection
Isolation Protection 2,000 VDC
Built-in TVS/ESD Protection
Power Reversal Protection
Environment
Operating -10 ~ 70°C (14 ~ 158°F)
Temperature -40 ~ 70°C (-40~158°F)
(ADAM-6017-D)
Storage Temperature -20 ~ 80°C (-4 ~ 176°F)
-40 ~ 80°C ( -40~176°F)
(ADAM-6017-D)
Operating Humidity 20 ~ 95% RH
(non-condensing)
Storage Humidity 0 ~ 95% RH
(non-condensing)